Gas Monitors, Sensors, and Analyzers Refineries • Drilling Rigs • Offshore Platforms • Petro-Chemical Plants • Gas Treatment Plants • Food Processing Industry • Waste Water Treatment Facilities Gas Monitors, Sensors, and Analyzers Refineries • Drilling Rigs • Offshore Platforms • Petro-Chemical Plants • Gas Treatment Plants • Food Processing Industry • Waste Water Treatment Facilities  
sensors arrow Sensors
arrow bullet PT205 Series
arrow bullet PT295 Series
arrow bullet PT395 Series
arrow bullet Ultra 1000 for Toxic and Combustibles
arrow bullet Ultra 1000-IR Infrared Sensors
monitors arrow Monitors
arrow bullet Alert II Dual Gas
arrow bullet PT500 Multichannel
arrow bullet PT1008 Multichannel
arrow bullet PT1016 Multichannel
arrow bullet PT1032 Multichannel
arrow bullet PT900 Series
arrow bullet PT100 Sample Draw
 
monitors arrow Analyzers
arrow bullet PT605 - H2S
arrow bullet PT605 - CO2
arrow bullet PT700 - CO2
monitors arrow Portables
arrow bullet PT104 Quad Alert
arrow bullet PT301N Hydrogen Sulfide Gas Generators/Calibrator
   
Model PT395-H2S Hydrogen Sulfide Sensor
Printable PDF
Features
  • Microprocessor based modular design
  • Electrochemical Sensor Technology
  • Industry standard 4-20mA output
  • Three (3) Field adjustable Alarm levels
  • Field adjustable Alarm level
  • Single point Non-Intrusive calibration
  • Bright 3 digit LED display
  • Displays gas concentration in ppm, calibration prompts and sensor fault codes
  • Class I, Div 1, Suitable for use in Hazardous Location

Description

Model PT395-H2S is a microprocessor-based sensor designed to detect hydrogen sulfide in parts per million (ppm) level. The unit features easy one-man calibration initiated by simply activating a magnetic switch and applying the gas.

The complete sensor consists of a stainless steel sensor head assembly, a user connection board and a transmitter board assembly. All of the sensor electronics are enclosed in an explosion proof instrument box. The unit's modular design allows easy maintenance, troubleshooting and high reliability.

The unit provides a 4-20mA signal proportional to 0 to 100% of the detection range of the sensor and three (3) fully programmable alarm relays.

The sensor transmitter board includes a three (3) digit LED display for continuous indication of the gas concentration. The calibration mode, alarm and fault status of the sensor are also indicated on the digital display. In the normal operating mode the digital display and 4-20mA reading is proportional to the gas concentration detected by the sensor. In the calibration mode the digital display indicates the calibration status, alarm relay outputs are inhibited and analog signal output is set to 2 mA to avoid any false alarm by the control monitor. In the sensor fault mode the transmitter drops the output signal to < 1 mA.

Model PT395 Stand Alone Sensor for H2S Specifications


Sensor Type
Electrochemical

Measuring Range
0 to 100 parts per million (ppm)

Repeatability
± 2 % Full scale

Zero Drift
< 5% per year

Response Time
T90 < 30 seconds with 100% FS gas applied

Classification
Class I, division 1, Groups B,C &D

Operating Temperature
-4°F to +122°F (-20°C to +50°C)

Operating Humidity
15% to 90% RH, non-condensing

Mechanical Specifications
Length: 7 inches (178 mm)
Width: 5 inches (127 mm)
Height: 4.5 inches (114 mm)


Display
Bright 3 digit LED display

Status Indicators
Amber and Red alarm LED indicators for Low,
High and Fault Alarms.
Three-digit display for gas concentration,
calibration mode and sensor fault codes.



Approvals
CSA Approved
CSA Standard C22.2 No 30-M1985 &
C22.2 No 142-M1987

Input Power
14-28 VDC. 24 VDC nominal

Power Consumption
65mA @ 24 VDC

Alarm Relays
Fully programmable. 0 to Full scale range
of the sensor. Latching or Non-Latching.

Relay Ratings
SPDT Form "C" type Relay contacts
0.5 Amp @ 125 VAC or 2 Amps 30 VDC

Analog Output
Linear 4-20mA (300 Ohms max. load)
2.0 mA - Calibration mode
< 1.0 mA - Sensor malfunction

Calibration
Non-Intrusive activated by internal magnetic
switch

Cable Requirement
3 wire shielded cable. Max loop resistance of
20 Ohms @ 24 VDC nominal

Cable Entry Hub
¾" NPT Female

Other Toxic Gas sensors available