| Features |
 |
- Up to 8 channel of continuous monitoring
- Programmable for Oxygen Deficiency, Combustible and several toxic gas sensors
- Sensor diagnostic features.
- 5 Alarm Relay Contacts
- Field Adjustable Alarm Levels
- Large LC Display with back light
- Real time clock and non-volatile memory for data logging
- RS232/RS485 Serial Communication
|
|
 |
Description
Model PT1008 is a microprocessor-based multi-channel controller
that provides up to eight channels of continuous gas detection.
The controller is housed in a Nema 4X weatherproof enclosure.
PT1008 can be interfaced with any of Pem-Tech's toxic and
combustible gas sensors. The controller provides a front panel
user interface with alarm LED indicators and large LCD with
back light.
PT1008 allows each channel to be programmed for sensor type
and discrete alarm levels. Four fully programmable alarm relays
are provided. The alarm relays can be configModel PT1008
Multi-Channel Controller
ured to activate on any of the 8 channel's alarm levels for
use with external devices such as horn or beacon.
On the main control board along with a low power microprocessor
are real time clock and non-volatile memory for data logging.
The unit can store up to seven days of historical data and
200 alarm events. The historical data and the system configuration
report can be easily downloaded to a laptop computer.
|
Model PT1008 Multi-Channel Controller Specifications
|
Enclosure
Corrosion resistant Nema 4X Fiberglass with
stainless steel lockable latches.
Capacity
Up to 8 toxic and/or combustible sensor
connections.
Front Panel Indicators
- Alarm and Fault LED indicators
- Large 4 lines by 20 character LCD module
Front Panel Switches
- Programming sensor type and alarm levels
- Alarm Reset and Bypass/Inhibit mode
Electrical Classification
General Purpose
Operating Temperature
-10°F to +150°F (-23°C to +65°C)
Operating Humidity
5% to 100% RH, non-condensing
Mechanical Specifications
Height: 12 inches (304 mm)
Width: 12 inches (304 mm)
Depth: 8 inches (203 mm)
Weight 12 Lbs. (5.4 Kg)
Approvals
CSA & UL pending
Input Power
115/230 VAC . Standard
18-28 VDC (Battery backup systems)
|
Power Consumption
120mA nominal @ 24 VDC
180mA max. with all alarm relays active.
(Sensor power consumption not included)
Alarm Relays
Four fully programmable alarm relays and a
malfunction relay. Latching or non-latching, normally
open or normally-closed contacts.
Relay Ratings SPDT Form "C" type Relay contacts 10 Amps @ 250 VAC or 30 VDC
Peripheral & Interface
- RS232 Interface for historical data downloading
- Optional RS-485 MODBUS ® RTU Compatible with PLC's, SCADA and DCS systems.
Cable Connections
Ten each cable glands on the bottom of the enclosure.
3 wire shielded cable for each sensor
connection to control module. Max loop
resistance of 20 Ohms @ 24 VDC nominal
between the sensor and the Control modules
Warranty
Two years
|
|