PT2008-SS
Download Datasheet
Features
- Large Graphic display (240 x 128 Pixels)
- Optional Historical data Logging with Real time clock calendar
- Sensor interface: 4-20mA transmitter or Addressable serial IO type
- Eight (8) channels for analog sensors (PT295 series) or 24 addressable sensors (Ultra1000 series)
- Easy Configuration using keypad switches on the front panel
- Programmable sensor location or tags
- Programmable for various toxic and combustible gases, Pressure switches and pressure transducers.
- Six (6) fully programmable alarm relays and 1 Sensor malfunction or communication fail relay.
- Low power suitable for use in remote areas with solar power.
- Interface to Multiple Remote Relay modules
- Complete Digital data communication using RS485 MODBUS RTU protocol
- Optional Wireless Radio Interface Module. Operating Frequency 900 MHz
- Sensor Interface
- Standard 4-20mA transmitter (PT295 Series).
- Addressable Sensor with MODBUS RTU Communication. (Ultra1000 Series)
- Maximum of 8 analog sensors or 24 addressable sensors
- Enclosure
- Nema 4X Stainless Steel Enclosure with clear window
(Optional Purge Kit available for pressurized
enclosure)
- Operating Temperature
- Operating Humidity
- 15% to 90% RH, non-condensing
- Display
- 240 x 128 Pixels Graphic Display with back light
- Status Indicators
- Yellow and Red LED alarm Indicators
- Enclosure Dimension
- Length: 14 inches
- Width: 14 inches
- Height: 7 inches
- Historical data Logging
- Historical Alarm / Event Log with date and time stamp. Maximum of 300 Event log records. Data download to laptop computer using Windows Hyper Terminal utility program.
- Optional Radio Interface Module
- Typical Distances : 5 Miles Clear line-of-sight with a dipole antenna
- Up to 20 miles with high gain antenna
- Alarm Relays
- Six (6) Each Form “C” type relays
- Rated at 5 Amps AC/DC
- Input Power
- Internal 110/220 VAC power supply for standard 8 Channel Controller.
- Serial Interface
- RS-485 MODBUS RTU at 9600 Baud.